Pos.

Colour / status

Description

ST

green is on

The communication module is supplied with voltage and has a connection

to the basic device.

green is blinking

The communication module is supplied with voltage but is not connected to

the standard device (standard device is switched off, being initialised, or not

available).

ER

red is on

An error has occurred on the communication module.

MS

green

red

off

off

The communication module is not supplied with voltage.

off

on

The communication module is defective and must be replaced.

off

blinking

The error in the communication module can be removed.

on

off

The communication module works properly.

blinking

off

The communication module has not been completely configured yet or

configuration is faulty.

blinking

blinking

The communication module is in self-test mode.

NS

green

red

off

off

The communication module is not supplied with voltage via DeviceNet or

the ”Duplicate MAC ID” test has not been completed yet.

off

on

The communication module cannot access the bus ( e.g. ”Duplicate MAC ID”,

bus off, invalid baud rate etc.).

off

blinking

The error in the communication module can be removed.

on

off

The communication module works properly and has established a

connection to the scanner.

blinking

off

The communication module ...

z

works properly;

z

has completed the ”Duplicate MAC ID” test;

z

has not yet been integrated by the scanner.

blinking

blinking

The communication module ...

z

is in error status;

z

has received and accepted a telegram for identifying the faulty devices

(”Identify Communication Faulted Request”).

DE

red is on

The communication module is not accepted by the standard device (see

notes given in the documentation of the standard device).

Advertising