Single-axis controllers
Wiring
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
121
EDS94SPP101 EN 7.1
4.6.6
Devices in the range 145 ... 695 A (75 ... 370 kW)
Device size 8S
SSP94KL08S
Fig. 4-26
Arrangement of the power connections
Tip!
The barrier between mains input and power terminals can be dismounted to
have more free space for wiring.
Motor
Terminal X105
Marking
Description
U
V
W
Motor phases
SSP94KL0X8
Connection for the PE conductor on the motor side with M8 ring
cable lug
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Device size 8S:
Flexible
With wire end ferrule
95
000
14
124
Inbus 5
M8 ring cable lug
95
000
9.5
84
WAF 13