Power supply modules
Wiring
Terminal assignment
6
253
EDS94SPP101 EN 7.1
6.6.10
Terminal assignment
The wiring area of the power terminals is designed for the cables being routed upwards
and/or downwards. Usually the AC mains cables come from above. When filters are used,
the connection cables are fed from below (for filters mounted beside the module) or from
above (for filters mounted above the module). The protection against contact in the cover
can be removed accordingly.
To improve the cable handling, the cable cross-section can also be divided onto two cables.
The ring cable lugs used must not exceed the dimensions specified here.
ƒ
E94APNE1004 (device size 4, connection M8): max. cable lug width 20 mm
ƒ
E94APNE2454 (device size 5, connection M10): max. cable lug width 33 mm
S94PN10050
Fig. 6-10
Arrangement of the power connections