Dc-bus operation, Rated data dc fuses – Lenze 9400 Manual User Manual

Page 326

Advertising
background image

DC-bus operation

Rated data

DC fuses

8

326

EDS94SPP101 EN 7.1

Fuse the individual +UG/-UG cables to protect the DC-bus connection. The DC-bus

connection is protected against damage through a DC earth fault or short circuit in a

device.

Controller/DC fuse assignment

Type

Rated value

Type

Size

Number per

[A]

(SIBA)

[mm] or size

+UG/-UG

Multi Drives
E94AMxE0024

E94AMxE0034

E94AMxE0044

20

EFSGR0200AYHz

14 x 51

1

EFSGR0200AYIz

22 x 58

E94AMxE0074

E94AMxE0094

32

EFSGR0320AYHz

14 x 51

EFSGR0320AYIz

22 x 58

E94AMxE0134

E94AMxE0174

63

EFSGR0630AYIz

22 x 58

E94AMxE0244

E94AMxE0324

100

EFSGR1000AYIz

22 x 58

Single Drives
E94ASxE0024

E94ASxE0034

16

EFSGR0200AYHz

14 x 51

1

EFSGR0200AYIz

22 x 58

E94ASxE0044

E94ASxE0074

32

EFSGR0320AYHz

14 x 51

EFSGR0320AYIz

22 x 58

E94ASxE0134

E94ASxE0174

63

EFSGR0630AYIz

22 x 58

E94ASxE0244

E94ASxE0324

E94ASxE0474

100

EFSGR1000AYIz

22 x 58

EFSGR1000ANVN

NH1

E94ASxE0594

E94ASxE0864

200

EFSGR2000ANVN

NH1

E94ASxE1044

250

EFSGR2500ANWN

NH2

E94ASxE1454

350

EFSGR3500ANWN

NH2

E94ASxE1724

E94ASxE2024

400

EFSGR4000ANWN

NH2

E94ASxE2454

500

EFSGR5000ANWN

NH2

E94ASxE2924

350

EFSGR3500ANWN

NH2

2 (in parallel)

E94ASxE3664

400

EFSGR4000ANWN

NH2

E94ASxE4604

500

EFSGR5000ANWN

NH2

E94ASxE5724

400

EFSGR4000ANWN

NH2

3 (in parallel)

E94ASxE6354

500

EFSGR5000ANWN

NH2

E94ASxE6954

Tab. 8-7

z

K = indicator, N = no indicator

Advertising