Rated data (devices for 400/500V mains)
Operation at rated mains voltage 500 V
4
61
EDS94SPP101 EN 7.1
Device size 8S ... 10
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
LN
[V]
U
LN
[V]
f [Hz]
3/PE AC
500
400 - 0 % ... 550 + 0 %
48 - 0 % ... 65 + 0 %
Mains current at I
aN
Output power
Motor power
(typical)
with external
mains choke
without external
mains choke
U, V, W
4 pol. ASM
Type
I
LN
[A]
I
LN
[A]
S
aN
[kVA]
P
aN
[kW]
P
aN
[hp]
E94ASxE1454
-
140
113
95
130
E94ASxE1724
-
166
134
110
150
E94ASxE2024
-
195
157
130
180
E94ASxE2454
-
237
191
160
215
E94ASxE2924
-
280
228
190
255
E94ASxE3664
-
354
285
235
320
E94ASxE4604
-
444
359
300
405
E94ASxE5724
-
553
446
375
510
E94ASxE6354
-
614
495
420
570
E94ASxE6954
-
672
542
460
625