Multi-axis controllers

Control terminals

5

202

EDS94SPP101 EN 7.1

Analog inputs, analog outputs
The controller features two analog inputs which are able to detect differential voltage

signals in the range ±10 V, e.g. an analog speed setpoint selection or the voltage signal of

an external sensor (temperature, pressure, etc.).

ƒ

The analog signal 1 can also detect a current setpoint.

The controller features two analog outputs, which can output internal analog signals as

voltage signals, e.g. for the control of analog indicating instruments or as a setpoint for

slave drives.

Electrical data
Analog input 1

Analog input 2

Level:

-10 ... +10 V

Resolution:

11 bits + sign

Scaling:

±10 V ≡ ±2

30

Conversion rate:

1 kHz

Analog input 1 as current input

(A1R and A1- bridged)

Level:

-20 ... +20 mA

Resolution:

10 bits + sign

Scaling:

For C00034 = ”1”

-20 ... -4 mA ≡-2

30

... 0

+4 ... +20 mA ≡0 ... +2

30

For C00034 = ”2”

±20 mA ≡ ±2

30

Conversion rate:

1 kHz

Open-circuit monitoring:

Configurable

Analog output 1

Analog output 2

Level:

-10 ... +10 V

(max. 2 mA)

Resolution:

11 bits + sign

Scaling:

±10 V ≡ ±2

30

Conversion rate:

1 kHz