Power supply modules – Lenze 9400 Manual User Manual

Page 257

Advertising
background image

Power supply modules

Control terminals

6

257

EDS94SPP101 EN 7.1

Design of the cables

ƒ

The cables used must comply with the approvals required for the location (e.g. UL).

ƒ

The effectiveness of a shielded cable is reached by:
– Providing a good shield connection through large-surface shield contact.
– Using only braided shields with low shield resistance made of tin-plated or

nickel-plated copper braid.

– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.

The following connections need not be shielded:

ƒ

24 V supply

ƒ

Digital signals (inputs and outputs)

Advertising