Regenerative power supply modules

Rated data (devices for 400/500V mains)

Fuses and cable cross-sections

7

274

EDS94SPP101-7.1

7.3.5

Fuses and cable cross-sections

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

230 ... 500

180 - 0 % ... 550 + 0 %

45 ... 65

Operation with external mains choke/mains filter
Type

Installation according to EN 60204-1

1)

Installation according

to UL

2)

FI

3)

c

d

L1, L2, L3 - Laying system

e

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E94AZMR0264xDB

E94ARNE0134

C32

-

10

6

-

30

10

-

E94AZMR0474xDB

E94ARNE0244

-

80

25

16

-

60

6

-

1)

The details are recommendations. Other designs/laying systems are possible (e.g. according to VDE 0298-4). The

cable cross-sections apply under the following conditions: the use of PVC-insulated copper cables, conductor

temperature < 70°C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.

2)

UL approved cables only, fuses and fuse holders must be used.

UL fuse: voltage 500 ... 600 V

3)

Universal-current sensitive earth-leakage circuit breaker

If several devices or cable lengths > 50 m are used, the circuit breaker may respond, depending on the cable type and

switching frequency.

c

Circuit breaker

d

Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

e

Fuse

Observe national and regional regulations