Multi-axis controllers, Warnings – Lenze 9400 Manual User Manual
Page 200
Multi-axis controllers
Control terminals
5
200
EDS94SPP101 EN 7.1
Terminal X2
Labelling
Description
GE
GND external supply
24E
24 V external supply via a safely separated power supply unit
(SELV/PELV)
9400SSP000X2
SB
State bus in/out (reference GE)
Terminal data
Conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
0.2 ... 2.5
24 ... 12
Spring terminal
With wire end
ferrule
Electrical data
24 V
Rated voltage
24 V
According to IEC 61131-2
Voltage range
19.2 ... 28.8 V
Residual ripple max. ± 5 %
Current consumption
Continuous operation: 2.4 A
Switch-on: 4 A for 100 ms
Controller enable: 4 A for 300 ms
Fuse
Circuit breaker with tripping
characteristic B or C,
Standard blade-type fuses
Looping through
Max. 7 devices with 2.5 mm
2
Fusing: 16/15 A
Max. 4 devices with 1.5 mm
2
Fusing: 10/10 A
Connectable cross-cuttings
See terminal data
Warnings!
Up to hardware version 1x, take the following tino consideration:
In UL-approved systems the fuse of the 24 V supply must not exceed 4 A.