Multi-axis controllers

Control terminals

5

200

EDS94SPP101 EN 7.1

Terminal X2

Labelling

Description

GE

GND external supply

24E

24 V external supply via a safely separated power supply unit

(SELV/PELV)

9400SSP000X2

SB

State bus in/out (reference GE)

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

0.2 ... 2.5

24 ... 12

Spring terminal

With wire end

ferrule

Electrical data
24 V

Rated voltage

24 V

According to IEC 61131-2

Voltage range

19.2 ... 28.8 V

Residual ripple max. ± 5 %

Current consumption

Continuous operation: 2.4 A

Switch-on: 4 A for 100 ms

Controller enable: 4 A for 300 ms

Fuse

Circuit breaker with tripping

characteristic B or C,

Standard blade-type fuses

Looping through

Max. 7 devices with 2.5 mm

2

Fusing: 16/15 A
Max. 4 devices with 1.5 mm

2

Fusing: 10/10 A

Connectable cross-cuttings

See terminal data

Warnings!

Up to hardware version 1x, take the following tino consideration:
In UL-approved systems the fuse of the 24 V supply must not exceed 4 A.