Single-axis controllers

Rated data (devices for 400/500V mains)

Operation at rated mains voltage 400 V

4

56

EDS94SPP101 EN 7.1

Operation with increased continuous power
If required, operation with increased continuous power can be activated for specific

controllers at the switching frequency 2 kHz. This operating mode can only be performed

under the following conditions:

ƒ

Controllers of the types E94ASxE1454 ... E94ASxE6954,

(device size 8S ... 10).

ƒ

The controllers require the versions SW: 04.00 and HW: 1C.
– ”Mode 1” is possible from SW: 03.00 and HW: 1C.

ƒ

For ”Mode 2” the mains voltage is ≤ 440 V.

ƒ

The maximum permissible ambient temperature inside the control cabinet is

40 °C.

ƒ

The maximum output current in C00022 is to be reduced according to the following

data for I

aMhc

.

ƒ

Operation with increased continuous power has to be activated in C01199 with

”Mode 1” or ”Mode 2”.
– For activation controller inhibit has to be set.

The currents deviating from the standard can be gathered from the following tables.

Note!

The ”activated” setting in C01199 is reset to ”deactivated” automatically

(without error message) if the above-mentioned conditions are not (no longer)

met.

ƒ

This, for instance, is also the case if the memory module is plugged into a

controller of device size 1 ... 6 (device replacement).