Regenerative power supply modules, Output data (on the dc side), Internal brake chopper data switching threshold u – Lenze 9400 Manual User Manual

Page 271: 727 v

Advertising
background image

Regenerative power supply modules

Rated data (devices for 400/500V mains)

Operation at a rated mains voltage of 500 V

7

271

EDS94SPP101-7.1

Output data (on the DC side)

Basis of the data
Mains

Voltage

U

DC

[V]

Voltage range

U

DC

[V]

Frequency range

f [Hz]

2/PE DC

705

565 - 0 % ... 775 + 0 %

-

Voltage

Frequency

Current [A]

Number of

phases

[V]

[Hz]

max. +45 °C c

max. +55 °C c

E94ARNE0134

In motor mode

705

0 (DC)

32

24

2

In generator mode

705

0 (DC)

16

12

2

E94ARNE0244

In motor mode

705

0 (DC)

57

43

2

In generator mode

705

0 (DC)

28.5

21.4

2

c

Temperature in the control cabinet

Output current and output power

100 %

5-s cycle

3-min cycle

Type

I

DC

[A]

P

DC

[kW]

I

DC

[A]

P

DC

[kW]

I

DC

[A]

P

DC

[kW]

E94ARNE0134

In motor mode

32

18.6

96

56.1

48

28

In generator mode

16

9.3

48

28.0

24

14

E94ARNE0244

In motor mode

57

33.8

171

101.4

86

50.7

In generator mode

28.5

16.9

87

50.6

44

25.3

100 %

Permanent rated values

5-s cycle

Cycle for the second-range
(0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value)

3-min cycle

Cycle for the minute-range
(60 s overload/120 s recovery time with 75 % of the permanent rated value)

Internal brake chopper data
Switching threshold U

BRmax

: 727 V

R

Bmin

[Ω]

I

BRmax

[A]

P

BRmax

[kW]

I

BRd

[A]

P

Bd

[kW]

t

Z

[s]

t

on

[s]

t

fp

[s]

Type
E94ARNE0134

27.0

26.9

19.6

13.2

4.7

150

15

15

E94ARNE0244

18.0

40.4

29.4

22.9

9.4

150

15

15

R

Bmin

Minimum brake resistance, nominal value ±10 %

I

BRmax

Peak current

P

BRmax

Peak braking power

I

BRd

Continuous current RMS - important for the dimensioning of the cables

P

Bd

Continuous braking power

t

Z

Cycle time, periodic load change with running time and recovery time

t

on

Running time

t

Z

- t

on

Recovery time

t

fp

Maximum running time without initial load and compliance with the recovery

time