3 rated data ( devices for 400/ 500v mains), 3 rated data (devices for 400/500v mains), Regenerative power supply modules – Lenze 9400 Manual User Manual

Page 265

Advertising
background image

Regenerative power supply modules

Rated data (devices for 400/500V mains)

7

265

EDS94SPP101-7.1

7.3

Rated data (devices for 400/500V mains)

Note!

The operation of the regenerative power supply modules is only permissible

with an assigned mains filter.

Assignment of filters to standard devices

Mains filter

Regenerative power supply module

Device size

Standard device

Installation

backplane

E94AZMR0264SDB

E94AZMR0264LDB

E94ARNE0134

E94AZPP0364

GG3

E94AZMR0474SDB

E94AZMR0474LDB

E94ARNE0244

E94AZMR0xx

SD

B -> ”short distance”

E94AZMR0xx

LD

B -> ”long distance”

General data

Power loss P

V

[W]

Type

Total (when operating with I

aN

)

Constant (control electronics only)

E94ARNE0134

150

40

E94ARNE0244

230

40

Power loss

Inductance

Regenerative

inductance

Voltage drop

P

V

[W]

L [mH]

L

gen

[mH]

Δ

U [V]

E94AZMR0264SDB

65

0.77 ±10 %

0.84 ±10 %

6.3

E94AZMR0264LDB

72

E94AZMR0474SDB

85

0.42 ±10 %

1.54 ±10 %

6.2

E94AZMR0474LDB

101

Advertising