Accessories (overview)

General accessories

Brake resistors

9

562

EDS94SPP101 EN 7.1

Operating conditions

Climatic

conditions

Class 3K3 to EN 50178

Without condensation, average relative humidity

85 %

Ambient

temperature

-10 °C ... +55 °C

Above 45 °C the permanent power P

d

is to be reduced by 2.5 %/°C

Installation

height

0 ... 4000 m amsl

Above 1000 m the permanent power P

d

is to be reduced by 5 %/1000 m

Mounting

location

z

The mounting location must comply with the device features mentioned in the chapter

”General data”.

z

Flammable materials or substances must not be placed in the vicinity of the brake

resistor.

z

The heat generated by the brake resistor must be dissipated freely.

Mounting

position

Standard

Vertically suspended with connecting cables at the bottom.

Variant

Horizontally standing with fixing bracket at the bottom.

The permanent power P

d

is to be reduced by 30 %!

Free spaces

Standard

at the top > 200 mm, to the sides > 25 mm, at the bottom > 100 mm

Variant

at the top > 200 mm, to the sides > 45 mm, at the bottom > 45 mm

Design and

project planning

z

Mean value of regenerative power < permanent power P

d

of brake resistor.

z

Regenerative power during braking time < heat quantity Q

B

of brake resistor.

z

Braking time < 10 % of cycle time (braking time + dead time).

z

Always connect the thermal contact and integrate it in a way into the system monitoring

that the mains supply will be switched off when the basic device is overheated.