Accessories (overview) – Lenze 9400 Manual User Manual
Page 394
Accessories (overview)
Function modules
Digital frequency
9
394
EDS94SPP101 EN 7.1
Rated data
Note!
Only one module per basic device may be used, either in module receptacle
MXI1 or MXI2.
Stop!
The output voltages on X9/4 and on X10/4 may only be charged at a total of
max. 150 mA.
If the output voltage on X9/4 is used, no digital input signal may be applied to
X9/8. In this case, the cable serves as a sensor lead. In case of a connection
error, the components connected to X9 are damaged.
Functions on X9
ƒ
Input for encoder signals with TTL level
ƒ
Voltage supply +5 V for encoder
ƒ
Sensor lead (sense) at regulated voltage supply (Lenze setting)
– max. control range of the voltage drop on the cable: 4 V (corresponds to 5 ... 9 V
output voltage on X9/4)
ƒ
Digital input signal (only with regard to unused or external voltage supply)
Functions on X10
ƒ
Output for encoder signals with TTL level, directly or simulated
ƒ
Voltage supply +5 V
ƒ
Digital output signal