Single-axis controllers

General data and operating conditions

4

40

EDS94SPP101 EN 7.1

”Single Drive”

supply conditions
AC-mains operation

Direct connection

DC-bus operation

Direct connection via terminals or busbars(can be retrofitted)

For more information, please see the chapter DC-bus

operation.

Power systems

TT

Operation permitted without restrictions.

TN
With grounded phase

Operation with additional measures permitted:

z

Overvoltage must be reduced to overvoltage category II

according to EN 61800-5-1.

z

Measures described for IT systems must be applied.

IT

Additional device-internal measure required (see (”Earthing

of internal EMC filters”,  103)

Motors

EN 60034

Only use motors suitable for inverter operation. Insulation

resistance: max. û ≥ 1.5 kV, max. du/dt ≥ 5 kV/μs

Operating conditions

Environmental conditions
Climate

Storage

IEC/EN 60721-3-1

1K3 (-25 ... +60 °C)

Transport

IEC/EN 60721-3-2

2K3 (-25 ... +70 °C)

Operation

IEC/EN 60721-3-3

3K3 (-10 ... +55 °C)

Current derating at +45 ... +55 °C:

Device size 1 ... 7: 2.5 %/°C

Device size 8S ... 10: 1 %/°C

Site altitude

0 ... 4000 m amsl

1000 ... 4000 m amsl: current derating of 5 %/1000 m

Pollution

EN 61800-5-1

Degree of pollution 2

Vibration resistance

(9.81 m/s

2

= 1 g)

Transport

IEC/EN 60721-3-2

2M2

EN 61800-2

2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s

2

200 ... 500 Hz: acceleration resistant up to 15 m/s

2

Operation

Germanischer Lloyd

5 ... 13.2 Hz: amplitude ±1 mm

13.2 ... 100 Hz: acceleration resistant up to 0.7 g

IEC/EN 60068-2-6

10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g