Power supply modules

General data and operating conditions

6

216

EDS94SPP101 EN 7.1

Mounting conditions
Mounting place

In the control cabinet

Mounting position

Vertical

Mounting clearances

Above/below

80 mm / ≥ 120 mm

Observe the device-related

notes on mounting.

To the sides

Side-by-side mounting without

any clearance

Connection conditions for DC power supply module
AC mains operation

Direct connection

DC-bus operation

Direct connection of axis modules via terminals or busbar

system

More information can be found in the Hardware Manual,

chapter ”DC-bus operation”.