Conditions for trouble-free DC-bus operation

Voltages

8

314

EDS94SPP101 EN 7.1

8.2

Conditions for trouble-free DC-bus operation

8.2.1

Voltages

Controllers can only be operated in a DC-bus connection, if the rated mains voltage/the

rated DC-bus voltage is the same. All brake choppers in the DC-bus system must have the

same thresholds.

8.2.2

Number of feeding points

The 9400 servo drives series has been designed for drive systems with a central AC mains

feeding point. For this you can use DC supply modules of different power categories.
Several AC mains feeding points are only permitted in drive systems with two single-axis

controllers of the same power category with inverse operation in motor and generator

mode. Your Lenze representative will be pleased to inform you about further possible

supply concepts.

8.2.3

Other conditions

ƒ

The entire DC power P

DC

must be provided by the feeding point (DC-supply module

or ”Single Drive” controller).

ƒ

The controllers in the DC bus may only start operation when the DC bus has been

completely loaded. I.e. controller enable may only be set after ”State bus OK” (see

terminal X2).

ƒ

Up to a total current of 100 A, devices up to 24 A (device sizes 1 ... 3) can be operated

via the integrated DC busbar. Maximum busbar overload for 60 s: 150 % * I

r

,

followed by a relief phase of 120 s: 75 % * I

r

.

ƒ

The DC bus must at no time be overloaded through the required maximum total

power. For this, a time/performance diagram has to be created and considered (see

Basic dimensioning).

ƒ

The cable protection measures described for the DC-bus operation must be

observed.