Regenerative power supply modules – Lenze 9400 Manual User Manual

Page 295

Advertising
background image

Regenerative power supply modules

Wiring

Earthing of internal EMC filters

7

295

EDS94SPP101-7.1

Implementing the measures
Proceed as follows to disconnect the internal connection between the filters and PE:
1. Remove IT insulating cap from the parking position c in the installation backplane.

– For this apply a screwdriver on the right or left and lever off the insulating cap.
– Optionally the insulating cap can be carefully removed using an appropriate pliers.

2. Attach IT insulating cap to the earthing jumper d until it clicks into place.

1

2

SSP94IT001

Fig. 7-8

Plugging the IT insulating cap onto the earthing jumper

Advertising