DC-bus operation

Introduction

General information on the accessories

8

313

EDS94SPP101 EN 7.1

8.1.4

General information on the accessories

Fuses in the DC bus
For device protection, multi-axis controllers up to 11 kW are equipped with a fuse in the

installation backplane. The fuse is only integrated into the current path if the busbar

system (X109) is used.
When operated in a DC-bus connection, single-axis controllers can be retrofit with a fuse

in the installation backplane for device protection (see busbar mounting set).
When the alternative terminal connections are used for DC-bus wiring, external fuses

must be integrated into both current paths (+UG/-UG).
Busbar mounting set
With the busbar mounting set (E94AZJA0xx) you can connect a single-axis controller via a

busbar to a DC bus, e.g. to provide additional brake power. The busbar mounting set also

includes the corresponding fuse.
DC-feeding point
With the DC-input module (E94AZEX100) you can establish the electrical connection

between the DC cables and the busbar. Multi-row or distributed arrangements are

possible.
Filters
RFI filters and mains filters are available for the devices connected to the AC mains (supply

modules or single-axis controllers).
Depending on the application, additional filters may be required for compliance with the

EMC regulations. When dimensioning the filters, please consider: