2 general data and operating conditions, Regenerative power supply modules – Lenze 9400 Manual User Manual

Page 263

Advertising
background image

Regenerative power supply modules

General data and operating conditions

7

263

EDS94SPP101-7.1

7.2

General data and operating conditions

General data

Conformity and approval
Conformity

CE

2006/95/EG

Low-Voltage Directive

Approval

UL

UL 508C

In preparation:

Industrial Control Equipment, File No. 132659

Mains data
Mains types

With earthed

point

Unrestricted use

The measures described for IT

systems must be observed

and carried out in all systems

(TN, TT and IT) and for all

interconnected modules

( 294)!

IT systems

Unrestricted use

Noise emission

EN 61800-3

With E94AZMR0xx4SDB mains filter: 6 x 10 m, C2

With E94AZMR0xx4LDB mains filter: 10 x 50 m, C2
Radiation: category C3

Noise immunity (according to requirements of EN 61800-3)

Electrostatic discharge

(ESD)

EN 61000-4-2

8 kV for air discharge,

4 kV for contact discharge to housing

Radio frequency

Conducted

EN 61000-4-6

150 kHz ... 80 MHz, 10 V/m 80% AM (1kHz)

Interference (housing) EN 61000-4-3

80 MHz ... 1000 MHz, 10 V/m 80% AM (1kHz)

Protection of persons and device protection
Enclosure

EN 60529

IP 20

Not in the wire range of

the terminals on the

motor side

NEMA 250

Protection against contact to

type 1

Insulation resistance

EN 61800-5-1

Overvoltage category III

Derating at and above 2000 m AMSL: overvoltage category II

Isolation of control circuits EN 61800-5-1

Safe mains isolation through double/reinforced insulation.

Short-circuit strength

EN 61800-5-1

DC-bus connection: not short-circuit-proof

Brake resistor connection: full

Control connections: full

Discharge current

EN 61800-5-1

> 3.5 mA

Observe regulations and

safety instructions!

Cyclic mains switching

Cyclic mains switching of five times in five minutes is fully

permissible.

Advertising