Accessories (overview)

Safety modules

SM301

9

413

EDS94SPP101 EN 7.1

Safety instructions

Danger!

When the request for the safety function is deactivated, the drive can restart

automatically. The behaviour can be set via the parameter ”Restart behaviour”

(C15300/1/2).
In the case of an automatic restart, you must provide external measures which

ensure that the drive only restarts after an acknowledgement (EN 60204).

Danger!

Danger to life through improper installation
Improper installation of the safety engineering systems can cause an

uncontrolled restart of the drives.
Possible consequences:

ƒ

Death or severe injuries

Protective measures:
Total cable length between X82 and the connected components (e.g. sensors,

devices, etc.) > 3 m:

ƒ

It is essential to shield the cable installed between X82 and the connected

components:

– Connect the shield at least to the shield support of the installation

backplane.

– If possible, connect the shield to the connected component as well.

Total cable length between X82 and the connected components (e.g. sensors,

devices, etc.) < 3 m:

ƒ

Unshielded wiring is permitted.

Warnings!

ƒ

Maximum surrounding air temperature: 55 °C.

ƒ

External fuse for 24 Vdc supply voltage. Rated 4 A DC fuse UL248-14.