Accessories (overview) – Lenze 9400 Manual User Manual

Page 417

Advertising
background image

Accessories (overview)

Safety modules

SM301

9

417

EDS94SPP101 EN 7.1

Connection data

Note!

Provide for a sufficient strain relief, so that the terminals are not pulled from

the plug connectors, in particular when you use rigid cables.

Cable cross-sections and tightening torques
Type

[mm

2

]

[Nm]

AWG

[lb-in]

Wire end ferrule,

insulated

0.25 ... 0.75

Spring terminal

24 ... 18

Spring terminal

Rigid

0.14 ... 1.5

26 ... 16

Stripping length or contact length: 9 mm

X82.1

Labelling

Description

This part of the terminal strip is not assigned.

GO

GND SD-Out1

O1B

Safe monitor SD-Out1, channel B

O1A

Safe monitor SD-Out1, channel A

This part of the terminal strip is not assigned.

X82.2

Labelling

Description

-

GND external supply

+

+24 V external supply via a safely separated power supply unit (SELV/PELV)

GIR

This part of the terminal strip is reserved.

RI1
GO

GND 24O

24O

+24 V external supply for the safe monitor SD-Out1 (SELV/PELV)

AIE

Error acknowledgement input (”Acknowledge In Error”)

CLA

Clock output for passive sensors, channel A (Clock A)

CLB

Clock output for passive sensors, channel B (Clock B)

X82.3

Labelling

Description

GCL

GND clock output

GI2

GND SD-In2

I2B

Sensor input SD-In2, channel B

I2A

Sensor input SD-In2, channel A

GCL

GND clock output

GI1

GND SD-In1

I1B

Sensor input SD-In1, channel B

I1A

Sensor input SD-In1, channel A

AIS

Restart acknowledgement input (”Acknowledge In Stop”, 1-channel,

bridged to X82.4/AIS)

Advertising