Accessories (overview), Dc input module components, Standards – Lenze 9400 Manual User Manual

Page 482: Operating conditions

Advertising
background image

Accessories (overview)

Components for operation in the DC-bus connection

DC-feeding point

9

482

EDS94SPP101 EN 7.1

DC input module components

Pos.

Description

Nameplate

X109

+UG busbar input

X110

-UG busbar input

X119

+UG cable input

X120

-UG cable input

X129

+UG cable output

X130

-UG cable output

Standards

Conformity and approval
Conformity

CE

2006/95/EC

Low-voltage directive

Approval

UL

UL 508C

Power Conversion Equipment, File No. 132659

GOST-R

51321.1-2000

51321.3-99

No. POCC DE.AN30.B08815

Protection
Enclosure

EN 60529

IP 20

NEMA 250

Protection against accidental contact acc. to type 1

Insulation resistance

EN 61800-5-1

Overvoltage category III

Reduction from 2000 m: Overvoltage category II

Operating conditions

Environmental conditions
Climate

Storage

IEC/EN 60721-3-1

1K3 (-25 ... +60 °C)

Transport

IEC/EN 60721-3-2

2K3 (-25 ... +70 °C)

Operation

IEC/EN 60721-3-3

3K3 (-10 ... +55 °C)

Current derating at +45 ... +55 °C:

Device size 1 ... 7: 2.5 %/°C

Device size 8S ... 10: 1 %/°C

Site altitude

0 ... 4000 m amsl

1000 ... 4000 m amsl: current derating of 5 %/1000 m

Pollution

EN 61800-5-1

Degree of pollution 2

Vibration resistance

(9.81 m/s

2

= 1 g)

Transport

IEC/EN 60721-3-2

2M2

EN 61800-2

2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s

2

200 ... 500 Hz: acceleration resistant up to 15 m/s

2

Operation

Germanischer Lloyd

5 ... 13.2 Hz: amplitude ±1 mm

13.2 ... 100 Hz: acceleration resistant up to 0.7 g

IEC/EN 60068-2-6

10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g

Advertising