Power supply modules – Lenze 9400 Manual User Manual
Page 241
Power supply modules
Mechanical installation
Devices in the range 100 ... 245 A (48 ... 119 kW)
6
241
EDS94SPP101 EN 7.1
Installation steps
Proceed as follows for the installation:
1. Prepare M5 threaded holes on the mounting plate according to the mounting grid.
– Always use all mounting points specified.
2. Screw the device onto the mounting plate. Do not yet tighten the screws.
– Use M5 screw and washer assemblies or M5 hexagon socket screws with washers.
3. Repeat step 2 for installation backplanes, which can be mounted directly adjacent to
one another.
4. Align all devices and installation backplanes.
5. If busbars are used: connect the busbars.
6. Tightly screw all devices and installation backplanes onto the mounting plate.
– Tightening torque: 3.4 Nm (30 lb-in).