Power supply modules, Warnings – Lenze 9400 Manual User Manual

Page 243

Advertising
background image

Power supply modules

Wiring

Safety notes for the installation according to U

L

or U

R

6

243

EDS94SPP101 EN 7.1

6.6.2

Safety notes for the installation according to U

L

or U

R

E94APNE0104/E94APNE0364

Warnings!

ƒ

Maximum surrounding air temperature: 55 °C.

ƒ

For use in a pollution degree 2 environment.

ƒ

Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 5000 rms

symetrical amperes, 500 V max.

ƒ

Voltage of the fuses must at least be suitable with the input voltage of the

drive.

ƒ

Use 60/75 °C copper wire only, except for control circuits.

Branch circuit protection

Type

Fuse [A]

E94APNE0104

15

E94APNE0364

40

E94APNE1004/E94APNE2454

Warnings!

ƒ

Maximum surrounding air temperature: 55 °C.

ƒ

For use in a pollution degree 2 environment.

ƒ

Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 18000 rms

symetrical amperes, 500 V max., when protected by H or K5 fuses.

ƒ

Voltage of the fuses must at least be suitable with the input voltage of the

drive.

ƒ

E94APNE1004: Use 60/75 °C copper wire only, except for control circuits.

ƒ

E94APNE2454: Use 75 °C copper wire only, except for control circuits.

Branch circuit protection

Type

Fuse [A]

E94APNE1004

100

E94APNE2454

250