3 dc-power requirements, Dc-power requirements, Dc-bus operation – Lenze 9400 Manual User Manual

Page 323: Rated data dc-power requirements

Advertising
background image

DC-bus operation

Rated data

DC-power requirements

8

323

EDS94SPP101 EN 7.1

8.4.3

DC-power requirements

Use the below tables to determine the power requirements of the devices used in the DC

bus and the device-dependent power loss for the rated mains voltage U

Lr

.

Power requirements P

ar

[W] with rated current

Type

U

Lr

= 230 V

U

Lr

= 400 V

U

Lr

= 500 V

Multi Drives
E94AMxE0024

500

900

1000

E94AMxE0034

900

1600

1700

E94AMxE0044

1400

2500

2700

E94AMxE0074

2500

4400

4800

E94AMxE0094

3300

5800

6400

E94AMxE0134

4700

8100

8900

E94AMxE0174

5900

10300

11200

E94AMxE0244

8400

14700

16100

E94AMxE0324

11500

20000

20200

Single Drives
E94ASxE0024

500

900

1000

E94ASxE0034

900

1600

1700

E94ASxE0044

1400

2500

2700

E94ASxE0074

2500

4400

4800

E94ASxE0134

4700

8100

8900

E94ASxE0174

5900

10300

11200

E94ASxE0244

8400

14700

16100

E94ASxE0324

11500

20000

21800

E94ASxE0474

16900

29300

32000

E94ASxE0594

19000

33100

40200

E94ASxE0864

30800

53600

58700

E94ASxE1044

37300

64800

70900

E94ASxE1454

-

90000

113000

E94ASxE1724

-

107000

134000

E94ASxE2024

-

126000

157000

E94ASxE2454

-

153000

191000

E94ASxE2924

-

182000

228000

E94ASxE3664

-

228000

285000

E94ASxE4604

-

287000

359000

E94ASxE5724

-

357000

446000

E94ASxE6354

-

396000

495000

E94ASxE6954

-

433000

542000

Tab. 8-5

Advertising