7 terminal assignment, Terminal assignment, Power supply modules – Lenze 9400 Manual User Manual
Page 249
Power supply modules
Wiring
Terminal assignment
6
249
EDS94SPP101 EN 7.1
6.6.7
Terminal assignment
Tip!
Complete the wiring of the installation backplane before plugging in the
standard device. The upper terminals of the installation backplane cannot be
connected with a plugged-in standard device.
Mains
Terminal X111
(left part)
Labelling
Description
L1
L2
L3
Connection of the mains phases L1, L2, L3
Connection for the supply-side PE conductor with M5 ring cable lug
SSP940X111
Terminal X112
(right part)
Labelling
Description
L1
L2
L3
Alternative connection at the bottom: mains phases L1, L2, L3
Connection for the supply-side PE conductor with M5 ring cable lug
SSP940X112
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Device sizes 1 + 2:
flexible
with wire end ferrule
2.5
12
0.5 ... 0.6
4.5 ... 6.2
PZ0
Device size 3:
flexible
with/without wire end
ferrule
10/16
6
1.2 ... 1.5
10.6 ... 13.3
PH1