6 wiring, 1 important notes, Important notes – Lenze 9400 Manual User Manual

Page 242: Power supply modules

Advertising
background image

Power supply modules

Wiring

Important notes

6

242

EDS94SPP101 EN 7.1

6.6

Wiring

6.6.1

Important notes

Danger!

Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains

disconnection.
Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes before

working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

Danger!

Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800-5-1. Especially:

– Fixed installation

– PE connection must conform to standards (PE conductor diameter

10 mm

2

or PE conductor must be connected twice)

Stop!

No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the maximally permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains fluctuations and

voltage peaks.

Advertising