8 wiring of control connections, Wiring of control connections, Regenerative power supply modules – Lenze 9400 Manual User Manual

Page 300: Danger, Stop

Advertising
background image

Regenerative power supply modules

Wiring

Wiring of control connections

7

300

EDS94SPP101-7.1

DC bus

Terminal X111

(right part)

Labelling

Description

+UG

-UG

Alternative option for DC-bus voltage connection (compatible to

9300 series)

E94ARNE0244: maximum current I

dc

= 50 A

SSP940X111

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Device size 3:

Flexible

With wire end ferrule

10

6

1.2 ... 1.5

10.6 ... 13.3

PH1

External brake resistor

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Device size 3:

Flexible

With wire end ferrule

10

6

1.2 ... 1.5

10.6 ... 13.3

PH1

7.6.8

Wiring of control connections

Danger!

Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains

disconnection.
Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes before

working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

Stop!

The device contains components that can be destroyed by electrostatic

discharge!
Before working on the device, the personnel must ensure that they are free of

electrostatic charge by using appropriate measures.

Advertising