Regenerative power supply modules

Wiring

Wiring of control connections

7

301

EDS94SPP101-7.1

Tip!

Parameter setting and configuration can be carried out using the

L-force »Engineer«. For this purpose the Online Help and the Software Manual

for the standard device will guide you.

System bus CAN on board

Terminal X1

Labelling

Description

Pin 2

CAN-LOW

Pin 3

CAN-GND

Pin 7

CAN-HIGH

9400SSP000X1

(Housing)

CAN-Shield

24 V supply

Terminal X323

Labelling

Description

GE

GND external supply

SSP9400X11

24E

24 V external supply through safely separated power supply unit

(SELV/PELV)

IEC 61131-2, 22.8 ... 28.8 V, residual ripple max. ±5 %

Current during operation: 450 mA

Starting current: max. 4 A for 100 ms

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

0.2 ... 2.5

24 ... 12

Spring terminal

With wire end

ferrule

Stripping length / contact length: 10 mm

Terminal X2

Labelling

Description

GE

GND external supply

24E

24 V external supply via a safely separated power supply unit

(SELV/PELV)

9400SSP000X2

SB

State bus in/out (reference GE)

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

0.2 ... 2.5

24 ... 12

Spring terminal

With wire end

ferrule