2 self tuning of the speed regulator – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 116

Advertising
background image

GEI-100332Ga

——— CONVERTER OPERATION ———

5

40

5.3.5.1.1 Checking current regulator performance using parameter Eint

While running the drive, monitor the parameter (Eint), located under menu heading “Current Regulator”. This

measure an average internal current error.
Its value should be close to zero, but values dynamically changing between -40 and 40 are acceptable. The drive

must have at least 30% load for this reading to be considered as a valid performance measurement. If

adjustments are needed, make small changes to the parameter (Current regulator\Arm inductance) to fine tune

(Eint) to an acceptable value.
- If Eint is positive value, increase “Arm inductance” value.
- If Eint is negative value, decrease “Arm inductance” value.

5.3.5.2 Self tuning of the speed regulator

Speed Self tuning identifies the total Inertia value at the motor shaft ( Kg*m

2

), the friction value (or Loss com-

pensation) in N*m and computes the Proportional and Integral gains of the speed regulator.

Warning !

This procedure requires free rotation of the motor shaft coupled to the load. Start/Stop

command is disregarded, therefore it can not be used on drives with limited travel.

Caution !

The test is performed using the torque limit value set in Test T curr lim parameter. The

torque is applied stepwise, with no ramp (profile), therefore the mechanical transmis-

sion must not have significant backlash, and it must be compatible with operation at

the torque limit set in Test T curr lim parameter. The user can reduce the torque limit

to a suitable value via theTest T curr lim parameter.

n

ote

!

-

Application where the system inertia coupled to the motor shaft is much higher than

the motor inertia value , increase the Test T curr lim parameter to avoid “Time out”

error.

-

This procedure is not suitable for use with “hoist” or “elevator” drives.

Preliminary operation before the correct execution of the Speed self tuning procedure is the appropriate calcula-

tion of the Torque const parameter.

Set the motor name plate data parametrs:

Motor max speed

Set the maximum motor speed value

Flux weak speed

Motor max speed percentage where the flux weakening range starts. (Crossover

point)

T Current limit +/-

Set the nominal motor current value

Motor nom flux

Set the Motor nom flux in Amps.

Max out voltage

Set the maximum armature voltage value

With speed regulator self tunig performed, the above parameters value can be changed according to the

application without Torque const parameter modification.

-

Set the motor shaft direction: Forward or Reverse via the Fwd-Rev spd tune parameter

-

Select the torque current value to be used during the test via the Test T curr lim parameter

Advertising