DV-300 Adjustable Speed Drives

——— CONVERTER OPERATION ———

5

7

- If the stop was caused by removing the voltage signal on terminal 13, both the signal at terminal 13 and

the command via the keypad are necessary to restart the drive. The signal at the terminals must be present

before giving the keypad command.

- The same applies accordingly to the enabling of the drive via the Enable drive parameter.

5.1.5.1 Starting and stopping the drive

n

ote

:

The keypad must be enabled (see section 6.11.1) before performing these actions.

Enabling the converter

ENT

START UP

Enable drive

-/+

Enable drive

-/+

Disabled

+

ENT

Enable drive

-/+

Enabled

- Select the parameter Enable drive in the DRIVE STATUS or START UP or MONITOR menu.
- Press ENT
- Use the key + to choose “Disabled” or “Enabled”.
- Press ENT to confirm your entry.

Disabling the converter

ENT

START UP

Enable drive

-/+

Enable drive

-/+

Enabled

ENT

Enable drive

-/+

Disabled

-

- Select the parameter Enable drive in the DRIVE STATUS or START UP or MONITOR menu.
- Press ENT
- Use the key - to change the display from “Enabled” into “Disabled”.
- Press ENT to confirm your entry.

Start / Stop

W

arning

:

The keypad STOP can be used only when MAIN COMMANDS parameter is set to

digital.

STOP

START

- Start:

press the Start key.

- Stop:

press the STOP key.