Table 4.3.4: Wire adapter Kit and lugs suggested for UL approval

Device type

Terminals

Wire adapter kit

Recommended lugs

type

Kit bolt

size [mm]

Tightening

torque [Nm]

ILSCO type

Burndy type

6KDV3148...

U, V, W

-

-

-

-

-

C, D

EAM 1578

8

25

CCL-4/0-516

YA28-L3

PE

-

-

-

-

-

6KDV3224...

U, V, W

-

-

-

CCL-2/0-12

YA26-L6BOX

C, D

-

-

-

CCL-2/0-12

YA26-L6BOX

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

6KDV3280...

U, V, W

-

-

-

CCL-4/0-12

YA28-LBOX

C, D

-

-

-

CCL-4/0-12

YA28-LBOX

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

6KDV3336...

U, V, W

-

-

-

CCL-4/0-12

YA28-LBOX

C, D

-

-

-

CRA-300, CRA-300L

YA30-L

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

6KDV3400...

U, V, W

EAM 1579

10

50

-

YA30-L

C, D

10

50

-

YA31-L

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

6KDV3450...

U, V, W

EAM 1580

14

140

-

YA34-L

C, D

14

140

-

YA36-L

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

6KDV3560...

U, V, W

-

-

-

CCL-4/0-12

YA28-LBOX

C, D

-

-

-

CRA-250, CRA-250L

YA29-LBOX

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

6KDV3800...

U, V, W

EAM 1581

10

50

-

YA30-L

C, D

10

50

-

YA31-L

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

6KDV3850...

U, V, W

EAM 1581

10

50

-

YA30-L

C, D

10

50

-

YA32-L1

PE

-

-

-

CRA-2/0, CCL-2/0-38

YA26-LBOX

DV0122g

C

aution

!

The current in the protective conductor of the motor cable can be up to twice the value of the

rated current if there is an earth fault at the output of the DV-300 converter.

In the table above 2X.... means that two compression lugs of the specified type have to be used on the opposite

side of the bus bar. 4X... means that four compression lugs of the specified type have to be used on the same bus

bar, two for each side and one for each bolt hole.

Bolt, nuts and washers are factory mounted on output bus bars.
For sizes above 112 A the front terminal covers have to be removed when using the above listed lugs.