4.9.4 AC input contactors

n

ote

!

The contactor sizes must be selected based on the converter rated current. The dimensions

basis is the thermo current AC1, which is absorbed by the input during the rated functioning.

n

ote

!

The technical data of the contactors, as for example weights, dissipated powers, auxiliary

contacts etc. can be found in the appropriate data sheets.

4.9.5 Control power protection

The 115 VAC/230 VAC control power input, U2 & V2, for the DV-300 are required to be short circuit protected.
This protection can be provided by using standard time delay fuses, or circuit breaker.
The circuit breaker and/or time delay fuses must be selected to survive the short circuit available current of the

feeder source for this circuit, and the inrush current of the drive power supply.
The rating of the fuses or circuit breaker should be sized mainly to protect the wiring from the fuses/circuit

breaker connections to U2 & V2, and not nuisance trip or blow from the inrush current.

The table below, Table 4.9.5, lists the input current characteristics of the control power.

Table 4.9.5: Control power protection

Device

Regulation Power Supply

American

European

Card

Power

Rated input current

Inrush input current

115 V

230 V

115 V

230 V

6KDV3017

to ...

6KDV3148

6KDV3020

to ...

6KDV3185

SW1-31

60 W

1 A

0.5 A

20 A

10 A

6KDV3224

to ...

6KDV3850

6KDV3280

to ...

6KDV310H

SW2-32

110 W

1.2 A

0.7 A

15 A

7.5 A

GD0315g

The control power input is best served by a power source that is stabilized and buffered from the power system transients.

The control power of many drives can be fed from a single source, as long as proper distribution protection is provided.

For example, a 6KDV3017, with 480VAC input, has control power fed from a 2 KVA 480:115 transformer that

is panel mounted in the drive panel. The transformer primary is wired from the 480VAC drive incoming power

from the load side of the main power disconnect and is fused with Fusetron 600 V 5A FRS fuses. The wires from

the transformer secondary to the drive connection points U2 & V2 are 12 AWG.

No additional circuit protection is required, and control power is disconnected when the main power discon-

nected is off.

If the 2KVA transformer was mounted in a remote panel, a 250V/120V 10A 5kA interrupting CB could be panel

mounted near the Drive to locally turn off the Drive control panel.