6.17 TORQuE WINDER FuNCTION

The center wind function inside the DV300 converters is used to control winders and unwinders whose tension

regulation is carried out via an open or closed loop control.
Apart from calculation functions for torque, diameter, compensation and Taper tension, the system foresees the

calculation of the motor speed reference. Such function allows to use the drive on the four regulation quadrants

controlling both winders and unwinders, and to control the motor with a peripheral speed proportional to the

diameter in case of a break of the wound material.
The torque is adjusted according to the motor flux, thus meaning that the system is suitable to control motors

with a constant torque-power ratio.
The closed loop regulation foresees an analog input for the loading cell 0…10V, 0…20mA, 4…20mA.
The output of the center wind function is sent directly to the current limits; the specific parameters T current

lim +/- and the limits set by the programmable overload function are anyway active in order to protect both

the inverter and the motor; among the three possible settings the one with the lowest value is always the most

important.

Input / Output

Line spd source

Line speed sampling parameter. It is used exclusively for the diameter calculation. The

speed threshold, Ref speed thr, under which the calculation procedure is blocked, refers

to Ref line speed. It can be programmed as analog input or encoder input.

Ref spd source

Line reference sampling parameter. It is used exclusively for the calculation of:

- the inertia compensations

- the line speed reference.

It can be programmed as analog input or encoder input.

Analog inputs
Tension ref

Per cent tension reference; 10V (20mA) = 100%.

Tension red

Per cent decrease in the Taper tension; 10V (20mA) = 100%.

Diam preset 3

Setting of the starting diameter; 10V (20mA) = max. diameter.

Analog outputs
Roll diameter

Present diameter; 10V = max. diameter.

Act tension ref

Tension reference decreased by the Taper percentage; 10V = 100% Tension ref.

Torque current

Request for torque current; 5V = drive size.

W reference

Reference for angular speed, 10V = 100% Base omega.

Actual comp

Active compensation monitor (it sums up static, dynamic and inertial frictions); 5V =

drive size.

Digital inputs
Torque winder En

Enabling of the center wind function.

Diam calc Dis

Enabling of the diameter calculation.

Diam inc/dec En

If enabled and if winder, the calculated diameter can never decrease; if unwinder the

calculated diameter can never increase. It is used to improve the system stability.

Wind/unwind

Winder/unwinder selection: 0 = winder, 1 = unwinder.

Winder side

Selection of the winding/unwinding side: 0 = up, 1 = down