GEI-100332Ga

——— CONVERTER OPERATION ———

5

46

- Enable flux reg = Enabled (default)
- Flux reg mode = Voltage control
- Enable flux weak = Enabled
- Set Gen access = Flux reference and Gen amplitude to 70% of the rated field motor current (this to allow

the overshoot of the system).

- Increase the value of the Flux P parameter till the overshoot of the field current is lower than 4% (Field curr).
- Increase the value of Flux I untill the overshoot is higher than 4%, then reduce it slightly lower than 4% .

n

ote

!

Because of the high time constant, the rate of rise of the field current is limited . The increase

time with optimal scale conditions can be last several hundreds of milliseconds.

- Gen access = Disconnected
- Enable flux weak = Disabled
- Set Flux current min at the desired value
- Configure the analog outputs on the basis of your needs.
- Save the settings.

Figures 5.3.6.5 ... 5.3.6.7 show some examples of tuning of the Flux regulator

Figure 5.3.6.5: Above: Flux reference; Below: Flux

current. The regulator behavior is not good. Jumps

are due to field changing.

Figure 5.3.6.6: Above: Flux reference; Below: Flux

current. The reduction of the field current depends

on the field time constant. The reg has no influence.

Figure 5.3.6.7: Above: Flux reference; Below: Flux

current. The increment in the field current has no

jump. Variation compared to Fig. 4.5.7: Increase of

Flux P from 2 to 10%. Flux I = 5%.