GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

174

The LINK source must be associated to PI output PID [n

0

771]:

Source link 1 = 8192 + 771 = 8963

The LINK destination must be associated to the value of the integral component= parameter PI I gain PID [n

0

764]:

Destination link 1 = 8192 + 764 = 8956

The multiplier factor must be set to the value defined by the functioning tests above mentioned.

Mul gain link 1 = 40

It will be necessary to set:
Div gain link 1 = 1000

*

Input max link 1 = 1000

*

Input min link 1 = 100

**

Input offset link 1 = 0
Output offset link 1 = 0
Input absolute link 1 = OFF

*

The value 1000 is defined by PI top lim which will be in this case = 1 (correspondent to a maximum value

of PI output PID = 1000).

**

The value 100 is defined by PI bottom lim which will be in this case = 0.1 (correspondent to a minimum

value of PI output PID = 100).

With this configuration at minimum diameter it will correspond an integral gain = 40% and at maximum diameter

it will correspond to an integral gain = 4%, between the two setpoints the gain will change with an hyperbolic

characteristic.

P

I

I

gain

PID

100

1000

PI

output

PID

40%

4%

Fmax

F

20%

PI I gain PID =

(

Fo / Fatt x KI

)

[KI = 40%]

Fo

100

1000

200

500

8%

500

200

Figure 6.16.3.16: Relation between PI I gain PID and PI I output PID

The value of PI I gain PID will be displayed in the relative parameter of the submenu PI controls.

If necessary, using the LINK 2, it is possible to modify, dynamically, the proportional gain P gain PID.