DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

121

6.14.7 Stop control

FUNCTIONS

Stop control

[626]

Stop mode

[627]

Spd 0 trip delay [ms]

[628]

Trip cont delay [ms]

[630]

Jog stop control

This function is intended to help the system engineer to coordinate the AC input contactor with the drive enabling.

According to the selected mode the terminals 75 and 76 drive the ON/OFF of the AC input contactor.
Basically, when the drive receives the Start command the Relay 2 closes the AC input contactor, the drive waits

for a certain time the AC input voltage, syncronizes itself and starts the motor. When the drive stops , the mo-

tor goes to zero speed. When the zero speed is reached, the drive is disabled only when a “Spd 0 trip” delay is

elapsed. Then after the “Trip cont delay” the Relay 2 opens to remove the supply from the drive.

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Stop mode

OFF (0)

Stop & speed 0 (1)

Fast stp & spd 0 (2)

Fst / stp & spd 0 (3)

626

0

3

Stop & Speed 0

Stop & Speed 0

*

Relay 75 / 76

Spd 0 trip delay [ms]

627

0

40000

0

0

-

Trip cont delay [ms]

628

0

40000

0

0

-

Jog stop control

OFF (0)

ON (1)

630

0

1

OFF

OFF

-

Figure 6.14.7.1: Start and stop management