DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

95

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Enab multi rmp

Enabled (1) / Disabled (0)

243

0

1

Disabled

Disabled

-

Ramp selector

202

0

3

0

0

-

Acc delta speed0 [FF]

659

0

232-1

100

100

-

Acc delta time 0 [s]

660

0

65535

1

1

-

S acc t const 0 [ms]

665

100

3000

300

300

Dec delta speed0 [FF]

661

0

232-1

100

100

-

Dec delta time 0 [s]

662

0

65535

1

1

-

S dec t const 0 [ms]

666

100

3000

300

300

Acc delta speed1 [FF]

23

0

232-1

100

100

-

Acc delta time 1 [s]

24

0

65535

1

1

-

S acc t const 1 [ms]

667

100

3000

300

300

Dec delta speed1 [FF]

31

0

232-1

100

100

-

Dec delta time 1 [s]

32

0

65535

1

1

-

S dec t const 1 [ms]

668

100

3000

300

300

Acc delta speed2 [FF]

25

0

232-1

100

100

-

Acc delta time 2 [s]

26

0

65535

1

1

-

S acc t const 2 [ms]

669

100

3000

300

300

Dec delta speed2 [FF]

33

0

232-1

100

100

-

Dec delta time 2 [s]

34

0

65535

1

1

-

S dec t const 2 [ms]

670

100

3000

300

300

Acc delta speed3 [FF]

27

0

232-1

100

100

-

Acc delta time 3 [s]

28

0

65535

1

1

-

S acc t const 3 [ms]

671

100

3000

300

300

Dec delta speed3 [FF]

35

0

232-1

100

100

-

Dec delta time 3 [s]

36

0

65535

1

1

-

S dec t const 3 [ms]

672

100

3000

300

300

Ramp sel 0

Value 2

0

not selected (0)

Value 2

0

selected (1)

403

0

1

0

0

*

Ramp sel 1

Value 2

1

not selected (0)

Value 2

1

selected (1)

404

0

1

0

0

*

* This function can be assigned to one of the programmable digital inputs.

Enab multi rmp

Enabled

The Multi ramp function is enabled

Disabled

The Multi ramp function is disabled

Ramp selector

It is the word representaton of the two parameters Ramp sel 0 (bit0) and Ramp sel 1

(bit1). Used to change the ramp selection by changing only one parameter instead of

two. This allows to select different ramps via serial line or Bus instantaneously.

Acc delta speed 0

It defines together with Acc delta time 0 the acceleration ramp 0. Defined by the units

specified in the factor function.

Acc delta time 0

It defines together with Acc delta speed 0 the acceleration ramp 0. Defined in seconds.

S acc t const 0

Defines the acceleration curve for S-shape ramp 0. Defined in ms.

Dec delta speed0

It defines together with Dec delta time 0 the deceleration ramp 0. Defined by the units

specified in the factor function.

Dec delta time 0

It defines together with Acc delta speed 0 the acceleration ramp 0. Defined in seconds.

S dec t const 0

Defines the deceleration curve for S-shape ramp 0. Defined in ms.

Acc delta speed1

It defines together with Acc delta time 1 the acceleration ramp 1. Defined by the units

specified in the factor function.