——— FUNCTION DESCRIPTION ———

6

128

6.15.2 Saving parameters, loading default factory settings, life time

SPEC FUNCTIONS

[256]

Save parameters

[258]

Load default

[235]

Life time [h.min]

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Save parameters

256

-

Load default

258

-

Life time [h.min]

235

0.00

65535.00

-

Save parameters

Saving of parameters that are currently set by the user.

This command can also be given from keypad, when “Bus” through the Control mode

parameter, has been selected.

Load default

Loading of the default settings (“Factory” column in the parameter table).

Life time

Shows the operating time of the converter. This parameter counts the time in which the

converter is powered on (even if disabled).

Default values for individual parameters are factory set in the device. These values are shown in the “Factory”

column of the individual parameter tables. In order to obtain the values specific to your application when the

device is switched on, they must be saved via the Save parameters command after being set.
The factory default values can be re-loaded by selecting Load default. If these are not saved, the application

specific drive settings will still be available the next time the drive is switched on.
When the device is switched on the saved parameter set is loaded.

n

ote

!

The Tacho scale and Speed offset parameters are used for the fine scaling of the speed feed-

back circuit. When the factory set parameters are loaded (Load Default) these two parameters

do not change, so that a new scaling is not required!