GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 356

Advertising
background image

GEI-100332Ga

——— TROUBLESHOOTING ———

8

6

FAILURE

POSSIBLE CAUSES

The motor reaches the maximum speed immediately

Reference value set via terminals: Check whether the value varies from min. to max. value.

Potentiometer used for reference value setting: is there a 0V connection present?

Encoder/tachometer not connected, or incorrectly connected or not supplied:

Preset the Actual spd parameter in the DRIVE STATUS menu.

With the regulator disabled turn the motor clockwise (viewed from the front of the

shaft). The value indicated must be positive.

If the indicated value does not change or if inexplicable values are shown, check the

power supply and the cabling of the encoder/tachometer.

If the indicated value is negative, reverse the encoder connections. Exchange channel

A+ and A- or B+ and B-. Using a tachometer change the conductor polarity.

The motor accelerates too slowly

Ramp set incorrectly

Motor running at max. current

Motor overloaded

Converter too small

The motor decelerates too slowly

Ramp values and times incorrectly set

Braking current too low

With twoquadrant drives: moment of inertia too high.

The motor turns slowly even though the reference value = zero

Minimum speed selected

Interference due to unused analog input. Remedy: set unused analog inputs to OFF

Disconnect reference value on used analog input

If drive now stands still, the effect is due to the cable resistance

of the 0V cable.

If the drive is still turning: check if the speed reference is zero.

If it is not zero set Offset input xx parameter so that the drive

stands still. If it is zero set Spd offset parameter.

The motor thermic is active

Overloaded motor

Motor thermic protection relay incorrectly scaled

The motor is not supplying the max torque and the max power

Drive working at current limit

Check whether the value for Full load curr in the CONFIGU-

RATION menu is set correctly

Check the value for the current limitation

Advertising