GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 54

Advertising
background image

GEI-100332Ga

——— WIRING PROCEDURES ———

4

10

From the R-TPD32-GE regulation card, a 6KCV300 TBO card has been integrated on the regulation section

(terminals from 21 to 42). The integrated card is considered by the device as TBO “A”.

Table 4.4.6 - B: Terminal Assignment (terminals from 21 to 42)

Designation

Function

I/O

Max voltage

Max current

21

Analog out 1

Analog output 1
Reference point: Terminal 22
Factory set for Actual speed

O

±10V

5mA

22

COM analog output 1

Reference point of analog output 1

23

Analog out 2

Analog output 2
Reference point: Terminal 24
Factory set for Motor current

O

±10V

5mA

24

COM analog output 2

Reference of analog output 2

25

COM digital outputs

COM digital outputs (Terminals 26…29)

26

Digital output 1

Digital output 1
COM: Terminal 25
Factory set for Ramp +

O

+30V

50mA

27

Digital output 2

Digital output 2
COM: Terminal 25
Factory set for Ramp -

O

+30V

50mA

28

Digital output 3

Digital output 3
COM: Terminal 25
Factory set for Spd threshold

O

+30V

50mA

29

Digital output 4

Digital output 4
COM: Terminal 25
Factory set for Overload available

O

+30V

50mA

30

Supply digital

output

Supply voltage for digital outputs

I

+30V

depends on

the load

max 80mA

31

Digital input 1

Digital input 1
COM: Terminal 37
Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

32

Digital input 2

Digital input 2
COM: Terminal 37
Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

33

Digital input 3

Digital input 3
COM: Terminal 37
Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

34

Digital input 4

Digital input 4
COM: Terminal 37
Not Factory set

I

+30V

15V/3.2mA

24V/5mA

30V/6.4mA

37

COM digital inputs

COM of the digital inputs (Terminals 31…34)

38 … 42

Not used

T0240g

Advertising