GEI-100332Ga

——— FUNCTION DESCRIPTION ———

6

42

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Enable flux reg

ON / OFF

497

0

1

Enabled

Enabled

*

Flux reg mode

Constant current

Voltage control

External control (OFF)

469

0

2

Const. current (0) Const. current (0)

-

Enable flux weak

ON / OFF

498

0

1

1

1

*

Speed-0 f weak

ON / OFF

499

0

1

0

0

Flux reference [%]

500

0.0

100.0

0.0

0.0

**

Flux current [%]

234

0.0

100.0

-

-

**

Out vlt level

921

0.00

100.0

100.0

100.0

**/***

I field cnst 40

916

0.0

100.0

40.0

40.0

I field cnst 70

917

0.0

100.0

70.0

70.0

I field cnst 90

918

0.0

100.0

90.0

90.0

Set flux / if

919

0

1

0

0

Reset flux / if

920

0

1

0

0

Nom flux curr [A]

374

0.5

70.0

S

S

Motor nom flux

280

0.00

P374

P374

P374

* This function can be set on a programmable digital input.

** This parameter can be set on a programmable analog output.

*** This parameter can be set on a programmable analog input.

Enable flux reg

Enabling of the field converter

Enabled

Field converter Enabled

Disabled

Field converter Disabled.

The field current is zero

Flux reg mode

Operating mode of the field converter .

Constant current

The motor field works with a constant current. The current value

corresponds to the setting of the Motor nom flux parameter.

If any curve via the I field cnst parameters will be defined,

this value can be changed linearly, through Motor nom flux

(percentage of nominal flux Motor nom flux)

(see Flux /if curve paragraph 5.4.5)

Voltage control

The drive works with a regulation combined with torque and

constant power (armature and field regulation). Via the Max

out voltage parameter in the CONFIGURATION menu, is set

the max. armature voltage.

External control

The field is supplied through an external excitation (rectifier/field

converter).

Enable flux weak

Command for Voltage control.

Enabled

The field current corresponds to the value set via the Flux cur-

rent min parameter.

Disabled

The field current is regulated on the basis of the functioning

mode and on the drive working setpoint.

Speed-0 f weak

When this function is enabled, and the speed 0 threshold is reached, it will be produced

the minimum field current set via Flux current min.

Supposing that: Start = Low level and/or Fast stop = Low level

Set as field economy: