DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

73

Example 5:

Select input 1 to T current lim

10Volt or 20 mA on Analog input 1 corresponds to T current lim = 100 [%]

The application requires a signaling at 50 [%] via a digital output, with a tolerance band equal to ±2 [%]

Input 1 cp match assigned to a programmable digital output

Input 1 compare = 50 * 10000 / 100 = 5000

Input 1 cp error = 2 * 10000 / 100 = 200

6.12.3 Digital Outputs

I/O CONFIG

Digital outputs

[145]

Digital output 1

[1267]

Inversion out 1

[146]

Digital output 2

[1268]

Inversion out 2

[147]

Digital output 3

[1269]

Inversion out 3

[148]

Digital output 4

[1270]

Inversion out 4

[149]

Digital output 5

[1271]

Inversion out 5

[150]

Digital output 6

[1272]

Inversion out 6

[151]

Digital output 7

[1273]

Inversion out 7

[152]

Digital output 8

[1274]

Inversion out 8

[629]

Relay 2

[1275]

Inversion relay 2

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Digital output 1

145

0

77

Ramp + (8)

Ramp + (8)

Inversion out 1

Enabled (1) / Disabled (0)

1267

0

1

Disabled (0)

Disabled (0)

Digital output 2

146

0

77

Ramp - (9)

Ramp - (9)

Inversion out 2

Enabled (1) / Disabled (0)

1268

0

1

Disabled (0)

Disabled (0)

Digital output 3

147

0

77

Spd thr. (2)

Spd thr. (2)

Inversion out 3

Enabled (1) / Disabled (0)

1269

0

1

Disabled (0)

Disabled (0)

Digital output 4

148

0

77

Overld avail. (6)

Overld avail. (6)

Inversion out 4

Enabled (1) / Disabled (0)

1270

0

1

Disabled (0)

Disabled (0)

Digital output 5

149

0

77

Curr lim. state (4)

Curr lim. state (4)

Inversion out 5

Enabled (1) / Disabled (0)

1271

0

1

Disabled (0)

Disabled (0)

Digital output 6

150

0

77

Over-voltage (12)

Over-voltage (12)

Inversion out 6

Enabled (1) / Disabled (0)

1272

0

1

Disabled (0)

Disabled (0)

Digital output 7

151

0

77

Under-voltage (11) Under-voltage (11)

Inversion out 7

Enabled (1) / Disabled (0)

1273

0

1

Disabled (0)

Disabled (0)

Digital output 8

152

0

77

Over-current (14)

Over-current (14)

Inversion out 8

Enabled (1) / Disabled (0)

1274

0

1

Disabled (0)

Disabled (0)

Relay 2

629

0

77

Stop ctrl (23)

Stop ctrl (23)

Inversion relay 2

Enabled (1) / Disabled (0)

1275

0

1

Disabled (0)

Disabled (0)