6.14 FuNCTIONS

6.14.1 Motorpotentiometer

FUNCTIONS

Motor pot

[246]

Enable motor pot

[247]

Motor pot oper

[248]

Motor pot sign

[249]

Motor pot reset

The motor potentiometer function allows the speed of the drive to be adjusted by pressing a key. The speed is

then adjusted according to the defied ramp time.

Parameter description

No.

Value

Standard

Configuration

min

max

Factory

American

Factory

European

Enable motor pot

Enabled (1) / Disabled (0)

246

0

1

Disabled

Disabled

-

Motor pot oper

247

-

Motor pot sign

Positive (1) / Negative (0)

248

0

1

Positive

Positive

-

Motor pot sign +

-

**

Motor pot sign -

-

**

Motor pot reset

249

*

Motor pot up

No acceleration (0)

Acceleration (1)

396

0

1

*

Motor pot down

No deceleration (0)

Deceleration (1)

397

0

1

*

* This function can be assigned to one of the programmable digital inputs.

** This parameter can be assigned to a programmable analog output.

Enable motor pot

Enabled

The motor potentiometer function is enabled. The ramp receives

its reference value from the motor potentiometer function.

Disabled

The reference value potentiometer function is disabled.

Motor pot oper

By pressing the “+” and “-” keys of the keypad the drive can be accelerated or decelerated.

+

Accelerate

-

Decelerate

Motor pot sign

This parameter is only accessible via the keypad and via the serial interface or Bus.

When the drive is operated via the terminal strip, the parameters Motor pot sign +and

Motor pot sign - must be used. As for 6KDV3 ... Q2... converters the “Positive” func-

tion must be selected.

Positive

“Clockwise” rotation selected

Negative

“Counterclockwise” rotation selected

Motor pot sign +

Only for 6KDV3 ... Q4...! Selection of the “Clockwise” rotation direction when the

selection is carried out via the terminal strip. The Motor pot sign + parameter is linked

with the Motor pot sign - parameter via an XOR function. This means that the com-

mand (+24V) must be given only to one of the two terminals.

High

“Clockwise” rotation direction selected

Low

“Clockwise” rotation direction not selected