DV-300 Adjustable Speed Drives

——— FUNCTION DESCRIPTION ———

6

219

Speed

Time [s]

1

2

3

4

1
2
3
4

Acc delta speed [21]
Acc delta time [22]
Dec delta speed [29]
Dec delta time [30]

Speed

Time [s]

1

2

3

4

1

2

3

4

1
2
3
4

Acc delta speed [21]
Acc delta time [22]
Dec delta speed [29]
Dec delta time [30]

6KDV3 ... Q2

6KDV3 ... Q4

Figure 6.17.4.1: Acceleration and deceleration

Qstp delta time

Is defined in seconds. If “0 s” is entered, the ramp output follows the reference value

directly.

Quick stop

Activates the Quick stop ramp to stop the Drive.

The acceleration of the drive is defined as a quotient of the Acc delta speed and Acc delta time parameters. It

is the same for both rotation directions of the motor.
The deceleration of the drive is defined as a quotient of the Dec delta speed and Dec delta time parameters. It

is the same for both rotation directions of the motor.
The Quick stop function provides a second deceleration ramp for braking the drive to halt in the event of an

emergency. The deceleration of the drive using the Quick stop function is defined as a quotient of the Qstp delta

speed and Qstp delta time. It is the same for both rotation directions of the motor. This function is only available

via the serial interface or BUS.

6.18.5 Factor function

DRIVECOM

Face value fact

[54]

Face value num

[53]

Face value den

Dimension fact

[50]

Dim factor num

[51]

Dim factor den

[52]

Dim factor text

The factor function contains two factors, the Dimension factor and Face value factor. They are both expressed

as fraction numbers.
The dimension factor enables the drive speed to be defined in a machine-related dimension, e.g. kg/h or m/min.
Further information and examples are given in the section on the Configuration menu.