GEI-100332Ga

——— CONVERTER OPERATION ———

5

50

+

S

+

T

Field current Limits

Flux current max

Flux current min

Spd=0 Thr

Voltage reg P / I Base

Field reg P / I Base

Field controller

Field reg P / I

I field curve

Voltage regulator

T

M

C1

D1

Output Voltage

Flux
current
min

Flux
current
max

Energy saving

Field economy

Fld reg P gain

2 %

Fld reg I gain

1 %

Flux current %

Nom flux curr

10 A

Motor field curr

10 A

Ifield cnst40

40 %

Ifield cnst90

90 %

Ifield cnst70

70 %

Voltage P

30 %

Voltage I

40 %

Output voltage

Max. out voltage

500 V

Out vlt level

100 %

Flux current max

100 %

Flux current min

70 %

Enable flux weak

Disabled

Speed-0 f weak

Enabled

Motor field curr

10 A

Flux reg mode

Speed zero level

10 rpm

Set flux/if

0

Reset flux / if

0

Flux P base

3277

Flux I Base

3277

Voltage P base

1.8 A/V

Voltage I base

13.0909 A/V*ms

Enable flux reg

Flux reference

S

-

-

Figure 5.3.7.2: Blocks diagrams of field current regulator

Tuning procedure:

- Reset the curve flux/current via the Reset flux / if command (FLUX REGULATION \ Flux / if curve menu )
- Set the Motor nom flux

:

Motor nom flux parameter (FLUX REGULATION menu)

- Set the output voltage via the Max out voltage parameter (CONFIGURATION menu) and the correspondent

percentage (100%) in the Out vlt level parameter (FLUX REGULATION menu)

- Set the Flux regulator Flux reg mode = Constant current (FLUX REGULATION menu)
- Set the flux percentage at 100% via the Flux current max parameter (FLUX REGULATION menu)
- Operate the Drive speed, so that the Armature voltage (MONITOR\Measurements menu) corresponds to

the value previously set in Max out voltage (CONFIGURATION menu).

- Via the Flux current max parameter decrease the voltage displayed in Armature voltage, up to obtain an

output voltage equal to the 90% of Max out voltage.

Carry out the reading of the current in the Flux current parameter (FLUX REGULATION menu) and insert

it in the I field cnst 90 parameter (FLUX REGULATION\Flux if curve menu).

- Via the Flux current max parameters decrease the voltage displayed in Armature voltage, to obtain an

output voltage equal to the 70% of Max out voltage.

Carry out the reading of the current circulating in the Flux current parameter (FLUX REGULATION menu)

and insert it in the I field cnst 70 parameter (FLUX REGULATION\Flux if curve menu).

- Via the Flux current max parameters decrease the voltage displayed in Armature voltage, to obtain an

output voltage equal to the 40% of Max out voltage.