Table 4.3.3: cable section for ul approval – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual

Page 47

Advertising
background image

DV-300 Adjustable Speed Drives

——— WIRING PROCEDURES ———

4

3

Table 4.3.3: Cable section for UL approval

Device type

Terminals

Wire

AWG / kcmils

Terminal bolt

metric size [mm]

Tightening

torque [Nm]

6KDV3017...

U, V, W

10

5

6

C, D

10

5

6

PE

10

5

6

6KDV3035...

U, V, W

8

5

6

C, D

8

5

6

PE

8

5

6

6KDV3056...

U, V, W

4

5

6

C, D

4

5

6

PE

4

5

6

6KDV3088...

U, V, W

1/0

terminal block

12

C, D

1/0

terminal block

12

PE

2

terminal block

12

6KDV3112...

U, V, W

2/0

terminal block

12

C, D

2/0

terminal block

12

PE

2

terminal block

12

6KDV3148...

U, V, W

3/0

terminal block

12

C, D

4/0; kit required

terminal block

12

PE

2

terminal block

12

6KDV3224...

U, V, W

2 x 2/0

10

50

C, D

2 x 2/0

10

50

PE

2/0

8

25

6KDV3280...

U, V, W

2 x 4/0

10

50

C, D

2 x 4/0

10

50

PE

2/0

8

25

6KDV3336...

U, V, W

2 x 4/0

10

50

C, D

2 x 300

10

50

PE

2/0

8

25

6KDV3400...

U, V, W

2 x 300; kit required

10

50

C, D

2 x 350; kit required

10

50

PE

2/0

8

25

6KDV3450...

U, V, W

2 x 500; kit required

10

50

C, D

2 x 600; kit required

10

50

PE

2/0

8

25

6KDV3560...

U, V, W

4 x 4/0

10

50

C, D

4 x 250

10

50

PE

2/0

8

25

6KDV3800...

U, V, W

4 x 300; kit required

10

50

C, D

4 x 350; kit required

10

50

PE

2/0

8

25

6KDV3850...

U, V, W

4 x 300; kit required

10

50

C, D

4 x 400; kit required

10

50

PE

2/0

8

25

DV0121g

The following sizes are not provided with pressure connectors.
Any UL listed lug, sized for the indicated bolt and AWG cable, is suitable for use.
Compression lug from ILSCO manufacturer are suggested for sizes greater than 56A.

Advertising