10.4 LIST OF hIGh pRIORITY pARAMETERS

When a 6KCV300DGF is used a subset of the DV-300 parameters can be exchanged with the optional card through

the automatic synchronous communication. For more details see the 6KCV300DGF technical documentation.

Parameter

No.

Format

Value

Read/
Write

min

max

factory

T current lim + [CURR]

8

U16

0

2 * TOP_CURR

TOP_CURR

R/W

T current lim - [CURR]

9

U16

0

2 * TOP_CURR

TOP_CURR

R/W

In use Tcur lim+ [CURR]

10

U16

0

2 * TOP_CURR

-

R

In use Tcur lim- [CURR]

11

U16

0

2 * TOP_CURR

-

R

Current lim red [CURR]

13

U16

0

2 * TOP_CURR

TOP_CURR

R

T current ref 1 [CURR]

39

I16

-2 * TOP_CURR

+2 * TOP_CURR

0

R/W

T current ref 2 [CURR]

40

I16

-2 * TOP_CURR

+2 * TOP_CURR

0

R/W

T current ref [CURR]

41

I16

-2 * TOP_CURR

+2 * TOP_CURR

-

R

Speed ref 1 [SPD]

42

I16

-32767

32767

0

R/W

Speed ref 2 [SPD]

43

I16

-32767

32767

0

R/W

Ramp ref 1 [SPD]

44

I16

-32767

32767

0

R/W

Ramp ref 2 [SPD]

48

I16

-32767

32767

0

R/W

Control word

55

U16

R/W

Status word

56

U16

R

Ramp ref [SPD]

110

I16

-32767

32767

-

R

Ramp outp [SPD]

113

I16

-32767

32767

-

R

Speed ref [SPD]

118

I16

-32767

32767

-

R

Actual spd [SPD]

122

I16

-32767

32767

-

R

Adap reference [SPD]

183

I16

-32767

32767

4000

R/W

Enc 1 position [ENC_PLS] *

197

I16

-32767

32767

-

R

Enc 2 position [ENC_PLS] *

198

I16

-32767

32767

-

R

Enc 1 last time [ENC_TIM] *

204

U32

0

2

32-1

-

R

Enc 1 last time high [ENC_TIM] *

205

U16

0

65535

-

R

Enc 2 last time {ENC_TIM] *

206

U32

0

2

32-1

-

R

Enc 2 last time high {ENC_TIM] *

207

U16

0

65535

-

R

Speed reg output [CURR]

236

I16

-2 * TOP_CURR

+2 * TOP_CURR

-

R

Lock speed reg

322

U16

0

1

0

R/W

Enc 2 speed [SPD] *

420

I16

-37767

32767

-

R

Enc 1 speed [SPD] *

427

I16

-37767

32767

-

R

Flux current max

467

U16

819

16384

16384

R/W

Flux reference

500

U16

0

16384

16384

R

Pad 0

503

I16

-32768

32767

0

R/W

Pad 1

504

I16

-32768

32767

0

R/W

Pad 2

505

I16

-32768

32767

0

R/W

Pad 3

506

I16

-32768

32767

0

R/W

Pad 4

507

I16

-32768

32767

0

R/W

Pad 5

508

I16

-32768

32767

0

R/W

Pad 6

509

I16

-32768

32767

0

R/W

Pad 7

510

I16

-32768

32767

0

R/W

Pad 8

511

I16

-32768

32767

0

R/W

Pad 9

512

I16

-32768

32767

0

R/W

Pad 10

513

I16

-32768

32767

0

R/W

Pad 11

514

I16

-32768

32767

0

R/W

Pad 12

515

I16

-32768

32767

0

R/W

Pad 13

516

I16

-32768

32767

0

R/W

Pad 14

517

I16

-32768

32767

0

R/W

Pad 15

518

I16

-32768

32767

0

R/W

Advertising