Table 2.4.2.2: ac input curents – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual
Page 29
DV-300 Adjustable Speed Drives
——— DESCRIPTION, COMPONENT IDENTIFICATION AND SPECIFICATIONS ———
2
9
As for 6KDV3...Q2C / Q4G converters see Appendix A (GEI-100332C).
During start-up the threshold for the undervoltage message has to be set via the Undervolt thr parameter
(standard: 230 V).
n
ote
!
According the input voltage the switch S15.7/8 on the regulation board must be set as follows:
6KDV3...Q2A; 6KDV3...Q4E
S15.7 = OFF
S15.8 = OFF
6KDV3...Q2B; 6KDV3...Q4F
S15.7 = ON
S15.8 = OFF
6KDV3...Q2C; 6KDV3...Q4G
S15.7 = OFF
S15.8 = ON
n
ote
!
As for the operation of the DV-300 converters AC input reactors and interference suppression
filters are required. See section 4.10, “Reactors/Filters”.
The converters above 560 / 770 A (American / European) and the AC input reactors have a
discharge currents to ground higher than 3.5 mA. EN 50178 states that beside the ground
conductor another ground connection should be laid.
C
aution
!
Due to the increased discharge current involved, a fixed ground connection (without connec-
tors) for the filters of the DV-300 converter is required.
Table 2.4.2.2: AC input curents
American
Current on the
European
Current on the
Current on the
Power Supply Regulation
AC Input
AC Input
field AC Input
Power
Card
6KDV3017...
17.2 A
6KDV3020...
17.2 A
10 A
70W
SW1-31
6KDV3035...
34.4 A
6KDV3040...
34.4 A
10 A
6KDV3056...
60.2 A
6KDV3070...
60.2 A
10 A
6KDV3188...
75.6 A
6KDV3110...
94.6 A
14 A
6KDV3112...
96.2 A
6KDV3140...
120.4 A
14 A
6KDV3148...
127.2 A
6KDV3185...
159.1 A
20 A
110W
SW2-32
6KDV3224...
192.5 A
6KDV3280...
240.8 A
20 A
6KDV3280...
240.6 A
6KDV3350...
301 A
20 A
6KDV3336...
288.7 A
6KDV3420...
361.2 A
20 A
6KDV3400...
343.7 A
6KDV3500...
430 A
20 A
6KDV3450...
386.7 A
6KDV3650...
559 A
20 A
6KDV3560...
481.2 A
6KDV3770...
662.2 A
25 A
110W
SW3-32
6KDV3800...
687.4 A
6KDV310H...
860 A
25 A
6KDV3850...
730.4 A
25 A
GD0040g
*
Current reduction for higher temperatures, see “Permissible ambient conditions”.
** The overload size and duration depend on the overload cycle, see section 6.14.5, “Overload control”.
As for sizes above 850 / 1050 A (American / European) see Appendix A (GEI-100332C).